Setting up Row control for non-partitioned cabinets
In Row Control mode, adjacent EC units can be set up to work as one unit to work together to control the pressure
in commonly joined cabinets. This allows less than one EC per cabinet for controlling airflow in lower density
situations. Designate any of the EC units in the row as the “Master”, and then list all other IP addresses of units to
be controlled as shown.
Accounts and Passwords
The unit offers account security options that are entered on the Admin tab of the Config uration
page. There are three levels of account security:
Administrator: Password protects the Display, Alarms and Configuration pages.
Control Access: Password protects the Control Actions and Control Settings pages.
View-Only: Password protects the Sensors, PDA, WAP and XML pages.